| Home > Publications database > Assessment of Power Quality in an Industrial Facility: A Case Study at DESY Hamburg |
| Journal Article | PUBDB-2026-03040 |
; ; ; ;
2025
IEEE
New York, NY
This record in other databases:
Please use a persistent id in citations: doi:10.1109/OJIM.2025.3629874 doi:10.3204/PUBDB-2026-03040
Abstract: This article presents a comprehensive assessment of power quality (PQ) disturbances in the industrial power network of the Deutsches Elektronen-Synchrotron (DESY), a leading research facility for particle physics. The study leverages high-resolution measurements (7-days) from Fluke 435 Series II and long-term monitoring data (6-months) from Janitza UMG 512 analyzers to characterize PQ issues.Measurement data were collected from various substations and Points of Common Coupling (PCC) to evaluate harmonics, voltage fluctuations, flicker, and transient events. The high-resolution data (sampledat 500 ms) revealed voltage deviations of up to ±4%, current unbalance exceeding ±10%, and flicker spikes reaching 0.63 Pst, all attributed to nonlinear load dynamics and switching events. In total, 17voltage swell events and 12 dips were recorded, along with 6 transient disturbances linked to PETRA’s12-pulse converter operations. Also, voltage and current total harmonic distortion (THD) levels peakedat 3.6% and 7.5%, respectively, breaching IEEE 519 thresholds under dynamic loading. These findings highlight the necessity of coordinated PQ monitoring strategies and support the development of predictive,data-driven PQ management frameworks tailored to mission-critical industrial networks.
|
The record appears in these collections: |